Cooling Tower Net Fill and Crossflow Cooling Tower Fill

coolinf tower partsCooling Tower Net Fill


The Net fill (Non-glued assembly fill) have been specially designed for medium to strongly polluted cooling water, it focus of the development being on a high stability as well as on easy and economical installation. Therefore these fills are built from mechanically joint grids and are easily cleaned. The Net grid packings are high-performance fills which provide an optimized pressure drop.


Technical Data:

1) Length: 900mm

2) Width: 450mm

3) Flute: 19mm

4) Special heating exchange area: 125 square meter / cubic meter

5) Thickness: 1.8mm

6) Conection: wedged joint

7) Maximum total suspended solid: 300 ppm continuoous operation and can be bear under 500 ppm within 10 hours

8) Usage life: ≥ 20 years


coolinf tower parts

Counterflow Cooling Tower Fill

MC75—a film fill system designed for counterflow towers offering you several distinct advantages.

  • Assured Improved Thermal Performance—Crossed corrugations provide the surface area and turbulence to develop efficient heat transfer. The corrugations inherently establish uniform fill sheet spacing at 0.75".

  • Durability and Quality—MC75 fill is thermoformed from .015" thick, UV inhibited, chemically-resistant polyvinyl chloride (PVC). The flame spread rating is less than 25 per ASTM E-84 and is considered self-extinguishing. The material is extruded and manufactured to rigid specifications before forming.

  • Improved System Efficiency—Using Marley MC75 film fill in place of existing splash type fill in counterflow towers usually means reduced fill height, which translates into reduced pumping head. MC75 will also provide greater cooling tower capacity, which means your current performance level will require less fan energy.

• Easily Adapted to Your Tower Configuration—The fill pack depth (air travel) is variable to provide the proper heat transfer area within a single fill layer. If another layer of fill is necessary for situations where additional air travel is required, it will be limited to only one. Limiting the number of interfaces between packs minimizes restrictions that usually cause fill clogging. MC75 counterflow fill can be hung from structural members or it can be bottomsupported in virtually all counterflow cooling towers, regardless of a cooling tower’s age or manufacturer.

cooling tower fillcrossflow

Relevant Cooling Tower Fill: